/ Certification


                     BS 8580-1:2019 Water quality. Risk assessments for Legionella control (Published 2010, updated 2019)
                     BS 8580 1 acts as a code of practice with recommendations and guidance for assessing the risk of Legionnaire's disease associated
              BS 8580-1  with man-made water systems. Recently updated to ensure it aligns with HSG 274 among other Legionella guidance documents.


                     BS 8580-2:2022 Water quality. Risk assessments for Pseudomonas aeruginosa and other waterborne pathogens (2022)
                     BS 8580 2 provides detailed guidance on assessing the risks posed by P. aeruginosa in healthcare settings, and the implications
              BS 8580-2
                     for duty holders, responsible persons and the Water Safety Group.

              ECAU/EChAU classification for mixers:
              There are 4 basic characteristics and the letters E A U have the following meaning:
               - flow rate (E);
               - sound (A - acoustics);
               - endurance (U);
               - withstanding stress of alternated pressure from the ceramic cartridges.
              The C or Ch characteristics (like comfort, water savings and energy) correspond to the parameters of the products (dimensions, effort
              to control and water-saving system).
              The C characteristic refers to the domestic sector whilst Ch refers to public and commercial places (Care homes, non-medicalised retirement
              homes...).

              The modalities of the classification are specified here below:
                                               for mechanical mixers               for thermostatic mixers
                                         E 00  4 lpm ≤ Q < 6 lpm                   4 lpm ≤ Q < 6 lpm
                                          E 0  9 lpm ≤ Q < 12 lpm                  9 lpm ≤ Q < 12 lpm
                                  Q       E 1  12 lpm ≤ Q < 16 lpm                 12 lpm ≤ Q < 16 lpm
                         Flow    lpm      E    16 lpm ≤ Q < 20 lpm                 16 lpm ≤ Q < 20 lpm
                           E  measured     2
                              under 3 bar  E 3  20 lpm ≤ Q < 25.2 lpm              20 lpm ≤ Q < 25 lpm
                                          E 4  Q < 25.2 lpm                        Q < 25 lpm
                                        For bath controls, the minimum classification is E3
                                          C 1  Dimensions, effort to control       Dimensions, effort to control
                      Comfort   Type      C    Water-saving system                 Water-saving system
                           C               2
                                          C 3  Energy-saving system                Energy-saving system
                                         Ch 1  Dimensions                          Dimensions
                      Comfort   Type     Ch    Water-saving system                 Water-saving system
                          Ch               2
                                         Ch 3  Energy-saving system                Energy-saving system
                                          A 1  20dB (A).< Lap ≤ 30 dB (A)          20dB (A).< Lap ≤ 30 dB (A)
                     Acoustics   Lap      A    15dB (A).< Lap ≤ 20 dB (A)          15dB (A).< Lap ≤ 20 dB (A)
                           A    dB (A)     2
                                          A 3  Lap ≤ 15 dB (A)                     Lap ≤ 15 dB (A)
                                                                                   Mobile shutter mechanism: 500,000 cycles
                                               Mobile shutter mechanism: 175,000 cycles
                    Endurance  Number     U    Mobile spout: 200,000 cycles        Thermostatic cartridge: 50,000 cycles
                           U   of cycles   3                                       Mobile spout: 200,000 cycles
                                               Shower-bath diverter: 80,000 cycles
                                                                                   Shower-bath diverter: 80,000 cycles


              OTHER INTERNATIONAL CERTIFICATION









              European Water Label (EU)  TMV3 (UK)  WRAS (UK)      BELGAQUA (BE)    WATERMARK (AU)    KIWA (NL)









              DIN-DVGW (DE)    SINTEF (NOR)      PZH (PL)          ZNAK BUDOWLANY B (PL)  GA (HK)     WELS (HK)