Page 30 - Water_Controls_for_Healthcare
P. 30
/ Electronic controls
BIOSAFE: INFECTION CONTROL
Opens/closes automatically, Energy savings
BIOSAFE
with no manual contact The electronic mixers and taps do not require
DELABIE's electronic mixers and taps are operated much energy to operate. For battery-operated
by active infrared detection. models, DELABIE has chosen infrared active pulse
Flow opens when the detector senses hands technology, a low-power consumption solution.
and shuts off automatically when hands are removed The infrared beam is emitted intermittently,
from the detection zone. saving energy while ensuring effective detection.
No manual contact prevents the spread of germs Battery-operated models have an average lifespan of
by hand. 350,000 cycles (i.e. 3 to 6 years) depending on
the frequency of use. The Lithium batteries are widely
Anti-bacterial duty flush programme available, affordable and recyclable.
If a mixer or tap is not used for prolonged periods of The significant hot water savings provided by DELABIE's
time, water stagnates in the pipework, which favours mixers and taps also result in energy savings.
the development of bacteria (e.g. isolated points-of-
use, unoccupied rooms, etc.). DELABIE’s electronic Environmental labels
mixers and taps have a duty flush programme. The water and energy saving performance of DELABIE's
An automatic flush takes place for approximately electronic mixers and taps means that the buildings
60 seconds every 24 hours after the last use achieve the highest performance standards for
(programmable on some models). international rating schemes such as LEED, BREEAM
Reduced-stagnation
solenoid valve or HQE.
Reduced-stagnation solenoid valve For more information see page 211.
Most solenoid valves are fitted with a rubber membrane
behind which water stagnates and is not renewed.
This can lead to bacterial proliferation. SPECIFICALLY DESIGNED
DELABIE has developed a technology without
a membrane (patented system). Easy to install
With this piston-operated solenoid valve, water DELABIE's products are easy to install and
is drained and renewed with every use which reduces adjustments are kept to a minimum in order to save
niches where bacteria can develop. time during installation.
The solenoid valve's self-cleaning system
with a calibrated groove reduces the build-up of dirt. • Independent electronic control unit:
No manual contact Furthermore, its slow closure eliminates water-hammer. BINOPTIC and TEMPOMATIC 2 models
Depending on the model, there is an option to adjust
the presence detection distance, to change
Conventional DELABIE
mixer mixer the operating mode (ON/OFF or automatic)
9 lpm 4 lpm 85% WATER and change the duty flush settings.
0% 85% AND ENERGY SAVINGS The electronic control units are waterproof (IP65)
with diagnostic LEDs to facilitate servicing.
Water savings • Electronic unit and solenoid valve integrated
Compared to conventional mixers and taps, DELABIE's in the body of the mixer/tap*: TEMPOMATIC 4
electronic mixers and taps can offer maximum water and TEMPOMATIC 5 models
savings. They ensure the manager's water bills can be Can be installed on any isolated point-of-use,
reduced whilst preserving user comfort. for new builds as well as renovation.
• Automatic shut-off and split delivery - 6V Lithium batteries*:
The mixer or tap shuts off automatically when hands There are no electrical connections required.
are removed from the detection zone. Simply connect the flexibles to the supply pipes
4.8L 0.8L in the same way as for a conventional mixer/tap.
This removes the risk of waste through negligence.
The anti-blocking security activates to prevent No special adjustment is necessary; the mixer/tap
32 sec. 12 sec. the mixer or tap from flowing continuously. is ready to operate independently for 3 to 6 years.
The flow time is reduced to the necessary minimum A red LED will flash for 15 days to indicate that
Water savings per use the battery life is low. The batteries can be
(wetting, rinsing). changed without shutting off the water supply
• Regulated flow rate or removing the mixer/tap.
Some of DELABIE’s electronic mixers and taps are The batteries are directly accessed through the
regulated at 4 lpm. The other electronic mixers head of the tap (TEMPOMATIC 4), or via a battery
YEAR and taps are, however, regulated at 3 lpm. - 230/6V mains supply (plug in or recessed)*:
pack attached to the flexibles (TEMPOMATIC 5).
The flow rate remains constant regardless of
pressure variations in the system.
The flow rate can be adjusted from 1.4 lpm To operate, simply connect the flexibles to
WARRANTY (see Environmental labels) to 6 lpm. the supply pipes and connect the electrical supply
to the mixer/tap via a plug and socket or recessed
connection close to the basin.
This does not require any specific maintenance
(no battery changes).
* Depending on model
30-year warranty against any manufacturing defects.
50 years repairability.
28 Mixers & taps for washbasins